Free home inspection checklist

ELECTRICAL PANEL(S) PAGE

Free DIY Home Inspection Checklist

General Comments
  • DIY Tips: 
  1. Some houses possess multiple electrical panels. We suggest printing this section as many times as necessary to accommodate the number of panels at your property.
  •  All conditions listed below (if checked) require an additional inspection by a professional of this trade
  •  All conditions are considered a hazard if checked

Service feed is      UNDERGROUND    AERIAL 

Weather Head (Aerial Service)
  •  Overhead service is Okay
  • Weather head is damaged
  • Service mast is leaning / rusted / cracked / damaged
  • Service conductors are too small for this size home
  • Service conductors not attached to weather head mast or roof cleat
  • Roof cleat is loose or pulled away from roof deck
  • Bolts on roof cleat need to be sealed
  • Neutral wire disconnected from mast
  • Flashing into the roof is missing / needs sealant/ damaged
  • Service mast is located more then 48” from eave
  • Wire entering Weather head is closer than 18” to the roof deck
  • Service conductors not suggested to pass over the roof more than 6 feet
  • Service conductors must maintain these clearances:
  • 8 feet over flat roof
  • 10 feet over grade
  • 10 feet over deck within 3 feet
  • 12 feet over driveway
  • 14.5 over diving board
  • 15 feet over alley
  • 18 feet over road
  • 22.5 feet over swimming pool
  • Wire entering Weather head are frayed / connections are exposed
  • Service wires laying on the roof deck
  • Service mast suggested to be better supported
  • No drip loop observed
  • Service wires too close to trees / buildings
Underground Service 
  • Check to see if any trees are close to underground feeders
  • Exposed underground wires observed
  • Exposed service feeder wires above grade
Service Panel Cover
  •  SPC is Okay
  • SPC is damaged
  • SPC is loose
  • SPC hinges missing / damaged / loose
  • SPC missing
Dead Front Cover
  •  DFC is okay
  • DFC is missing
  • DFC is damaged
  • DFC is missing screws
  • DFC is screws are pointed and not blunt
  • DFC is missing breaker labels
  • DFC breaker labels are worn
  • DFC is missing knockouts
  • DFC is not tight to breakers leaving a gap
  • DFC is not original to panel / replaced / modified
  • DFC is rusted / deteriorated
Service Size
  • The service size is _________ amps
  • The panels rating is  __________ amps
Wiring Methods
  • The wiring appears to be Non Metallic cable (Romex)
  • The wiring is drawn through conduit 
Bus Bar
  •  The bus bar looks okay
  • The bus bar is scorched / damaged
  • The bus bar appears to have been replaced
Infrared Observations
  •  No visible issues
  • Heat in excess observed at one or more connections / breakers / wires
Circuit Breakers
  •  Circuit breakers okay
  • Damaged Circuit breakers
  • Circuit breakers not approved for this panel board
  • Circuit breakers scorched
  • Circuit breakers loose
  • Circuit breaker is tripped for unknown reasons
  • AFCI (blue button) recalled
  • GFCI breaker defective
  • Circuit breakers amps too large for appliance / circuit / wire
Panel Wiring
  • Wiring looks okay
  • Wires scorched
  • Wires are corroded or deteriorated
  • Wires loose in panel not terminated
  • Two or more wires into one breaker
  • Wire is too small for breaker size
  • Wire / circuit is not protected by breaker / fuse (direct tap)
Neutral / Grounding Bus
  • Panel appears to be bonded
  • No visible bond observed  (The bus bars appear to be floating)
  • Bus is deteriorated 
  • Two or more neutral wires under one terminal
  • Ground and neutral wire under one terminal
  • GROUNDING ELECTRODE CONDUCTOR disconnected
Equipotential Bonding
  • EQ bond is complete
  • EQ bond is not visible / missing
  • EQ bond was terminated in re-pipe
  • No EQ bond due to plastic water pipes
  • EQ bond present but not compete to gas and hot water pipes
  • EQ bond clamps loose
  • EQ bonding conductor is too small  ( < #8 AWG )
Wiring Type
  • The wire type is non metallic ( Romex)
  • The wire type is stranded wire pulled through conduit
  • The wire type is old Aluminum
  • The wire type is pre-1984 Non metallic ( Romex)
Grounding System
  • The GROUNDING ELECTRODE CONDUCTOR (GEC) was verified
  • There is no GEC installed
  • The GEC is incorrectly sized
  • The GEC is was not visible to verify
  • The GEC is spliced
  • There are two or more GROUNDING ELECTRODES
  • The  GEC has been nullified 
  • The GEC requires a bonding jumper
  • The GEC is subject to damage and not protected
  • The grounding rod electrode is exposed and not completely embedded
  • There is only one grounding electrode where two are required
SUB-PANEL
General comments
Sub Panel Service Panel Cover
  • SPC is Okay
  • SPC is damaged
  • SPC is loose
  • SPC hinges missing / damaged / loose
  • SPC missing
Sub Panel Dead Front Cover
  • DFC is okay
  • DFC is missing
  • DFC is damaged
  • DFC is missing screws
  • DFC is screws are pointed and not blunt
  • DFC is missing breaker labels
  • DFC breaker labels are worn
  • DFC is missing knockouts
  • DFC is not tight to breakers leaving a gap
  • DFC is not original to panel / replaced / modified
  • DFC is rusted / deteriorated
Sub Panel Service Size
  • The service size is _________ amps
  • The panels rating is  __________ amps
Sub Panel Wiring Methods
  • The wiring appears to be Non Metallic cable (Romex)
  • The wiring is drawn through conduit
Sub Panel Bus Bar
  • The bus bar looks okay
  • The bus bar is scorched / damaged
  • The bus bar appears to have been replaced
Sub Panel Infrared Observations
  • No visible issues
  • Heat in excess observed at one or more connections / breakers / wires
Sub Panel Circuit Breakers
  • Circuit breakers okay
  • Damaged Circuit breakers
  • Circuit breakers not approved for this panel board
  • Circuit breakers scorched
  • Circuit breakers loose
  • Circuit breaker is tripped for unknown reasons
  • AFCI (blue button) recalled
  • GFCI breaker defective
  • Circuit breakers amps too large for appliance / circuit / wire
Sub Panel Wiring
  • Wiring looks okay
  • Wires scorched
  • Wires are corroded or deteriorated
  • Wires loose in panel not terminated
  • Two or more wires into one breaker
  • Wire is too small for breaker size
  • Wire / circuit is not protected by breaker / fuse (direct tap)
Sub Panel Neutral / Grounding Bus
  • The neutral and grounding bus are separate 
  • The sub panel appears to be incorrectly bonded to the equipment panel board 
  • Neutral and grounding conductors are intermixed
Sub Panel Wiring Type
  • The wire type is non metallic ( Romex)
  • The wire type is stranded wire pulled through conduit
  • The wire type is old Aluminum
  • The wire type is pre-1984 Non metallic ( Romex)
Sub Panel Grounding System
  • The GROUNDING ELECTRODE CONDUCTOR is present
  • There is no GROUNDING ELECTRODE CONDUCTOR 
  • The GEC is disconnected

FREE Electrical DIY home inspection Checklist

If you’re one of those persons who needs to tackle tasks head-on, than this should be easy for you.  In spite of the fact that home inspection is traditionally performed by professionals, it shouldn’t stop you. In fact, it should inspire you knowing that the majority of inspectors out there likely know just slightly more than you do.  As a matter of fact, with only a few hours and an on-line course you too can be a home inspector here in Santa Clarita or California. Going into this inspection, armed with your personal knowledge, You tube and of course, our FREE diy electrical home inspection checklist you will do well.

Electrical doesn’t have to be scary

Inspecting the electrical system doesn’t have to be a frightening experience. As a matter of fact, its not at all that bad. Consider the fact that you will be performing a basic non intrusive evaluation should help. In the even that you may not feel comfortable performing this inspection you can alway opt to call a professional home inspection company who may perform this task for a nominal fee.

Summary
Review Date
Reviewed Item
FREE DIY home inspection Checklist
Author Rating
51star1star1star1star1star